Ran out of hot water? Here's how to troubleshoot (and replace if necessary) the controls and heating elements of most common residential 120, 208 and 240 volt electric water heaters. Please read this entire wiki before beginning the procedure. Click on any picture for larger, more detailed view.
Step 1

With power off, remove the upper (and if provided lower) access panel(s).
Step 2
Clear away any insulation blocking access or view of the controls (thermostat and high temperature switch) and heating element.
Step 3
Locate the parts below:
High Temperature Limit Switch: Has a reset button There will be (4) terminal screws / wires connected to it. Usually the top two terminals have wires that go up to the field wiring compartment that bring the power to the rest of the water heater's controls and heating elements.
Thermostat: Has a graduated, adjustable dial. The dial may indicate letters "A" "B" "C" etc., "warm, hot and hotter" or as in the case of the one pictured, the actual temperature in degrees.
Heating Element: Has two terminals with a wire connected to each. It is usually located below the controls and supports the controls with an a clip of some type.
Step 4
Test to ensure power is off. Set the meter for AC Volts and insert the black probe into the black or common jack, and the red probe into the red or Volts jack.
Step 5

Measure Voltage. Set the AC voltage range to the highest available. Touch the probes to the top terminals of the high temperature limit switch as shown in the image to the right. If desired, the range may be lowered to any desired - provided the range is greater than the voltage displayed at the highest range. If unable to prove power off, double check circuit panel.
Step 6
Set the multimeter to Ohms or Resistance. Observe the meter indication. If an analog type, the needle or pointer will be resting at over the higher resistance values (left-most position) this is an "open circuit" indication. If digital, it may display "OL" or "1" ("1" without trailing or leading zeros). This OL or 1 indication represents a value greater than the meter is capable of displaying (similar to the way a calculator does) for "overload" or "infinity". Infinity in high resistance range is also called an "open circuit" or "Open Loop" (OL). Take note of this open circuit indication for this meter (when in a voltage or current range is selected and the meter displays OL or 1, the measurement should be taken again after adjusting the range upward). If you are unsure what your meter should read in an "OL stituation", just leave the terminals unconnected to anything and not touching each other and switch the meter on, it should then indicate the resistance of the air between the terminals which should be infinity in normal conditions.
Step 7
Remove one wire from the heating element, it does not matter which.
Step 8
Connect the black test lead to the jack marked "Common".
Step 9
Connect the red test lead to the jack marked "Ohms" or "Resistance" if there are multiple jacks from which to choose.
Step 10
Set the range (if provided) to R x 1. If the meter being used does not provide for range selection, it is likely an "autoranging" type. This simply means that the meter will automatically adjust the range up or down as needed without any intervention by the user. This feature is far more common on digital meters than analog types. Most analog meters that do not provide manual range selection likely support only a single range. These meters are much more accurate indicating low values (such as 0 through 500k or 1M ohms) than higher values (such as those above 1M), but will work well for this procedure. Pay close attention to the display of an autoranging digital meter when reading - there is a huge difference between 20, 20K and 20M ohms. A "K" indicates thousands, and an "M" indicates millions. The examples above would correctly be read as 20 ohms, 20,000 ohms (20K ohms or 20 kilo ohms) and 2,000,000 ohms (2 meg ohms or 2 million ohms), each is 1000 times larger than the previous.
Step 11

Press the metal tips of the test probes together. The analog meter pointer should move to lowest values of the resistance scale (or fully to the right). The digital meter should indicate 0 or a "very low" value approaching zero. Locate the "Zero Adjust" knob and turn so that the the meter indicates "0" (or as close to "0" as possible). Most digital meters do not have this Zero Adjust feature. Once "zeroed", this needle position on the dial is the "short circuit" or "zero ohms" indication for this range of this meter. The meter must be zeroed if the resistance range is changed. Measured resistance values will be inaccurate if unable to properly zero the meter.
Step 12
Replace batteries if needed. If unable to obtain a zero ohm indication on an analog meter, this may mean the batteries are weak and should be replaced. Retry the zeroing step above again with fresh batteries. Digital meters often graphically display the battery's level of discharge or simply an indication to replace the battery. Check the meter manual for help determining the battery charge state.
Step 13

Press the probe tips against the terminals of the heating element (one probe to each screw). Read the meter display. Look for a range multiplier (a "K" or "M" in the display) to be sure the value displayed is really ohms, not kilo ohms (K) or meg ohms (M).
Step 14

Be aware that a "good" heating element will read a very low value (between 10 and 20 ohms depending on wattage of the element). Determine correct resistance value: According to the nameplate of a typical residential water heater, it is rated "volts 240" "watts 4500 / 4500" (a "4500 / 4500" watt rating simply means there are two heating elements and they are 4500 watts each). In the procedure outlined in this wiki, the electrical system voltage is 208. This means that the wattage for the elements are 3500 / 3500 as indicated on the lower portion of nameplate data decal.
Step 15
Determine resistance in ohms. Since this is a purely resistive AC circuit, we can use Ohm's Law for DC circuits. To do this, we simply divide volts by amps. Since the nameplate only provides watts and volts (4500 / 4500 watts at 240 volts or 3500 / 3500 at 208 volts electrical info, the current in amps must be calculated before determining the resistance in ohms below:
- Calculate amps, divide watts by volts: 4500 watts / 240 volts = 18.25 Amps, (The element under test in the pictures: 3500 watts / 208 volts = 16.8 amps)
- Continue with these results to calculate ohms, divide volts by amps: 240 volts / 18.25 amps = 13.2 ohms (The element under test in the pictures: 208 volts / 16.8 amps = 12.3 ohms). A "4500 / 4500" or 3500 / 3500 rating simply indicates the wattage value for the upper and lower elements since at no time are both energized at the same time. The examples above are for two 4500 or 3500 watt elements (very common values).
- A good heating element will read no more than about + or - 20% of these calculated values. If not, the heating element is suspect, should be considered for replacement (described later). The range of acceptable resistance is variable because resistance is determined by the material's resistivity, length & width and temperature. Changing any of these values can significantly increase or reduce measured resistance. Since the element material's resistivity, length & width are kept constant in the manufacturing process, only the temperature can be varied for the element under test.
Step 16
Check for a grounded element. Prepare the meter by setting the meter to highest resistance scale.
Step 17
Hold the probes at the end of the test leads together. The analog meter pointer should move fully to the lowest values of the resistance scale (to the right). The digital meter should indicate a "low" value very close to zero. Locate the "Zero Adjust" knob and turn so that the the meter indicates "0" (or as close to "0" as possible). The digital meter may not have this Zero Adjust feature. Note that this position is the "short circuit" or "zero ohms" indication for this particular resistance range of this meter. Always "zero" the meter when changing resistance ranges.
Step 18

Press the red probe against either terminal screw of the heating element. Press the black probe firmly against the metal tank or the heating element mounting nuts or screws (not the other terminal screw). Scrape the metal to ensure a good contact. The meter should display the "infinity" indication as described above in the meter setup. If the meter displays a value other than a very high value (millions of ohms), preferably infinity, the element should be replaced, described later.
Step 19
Repeat the procedure for the lower heating element.
Step 20
Reconnect the wire at each heating element.
Step 21
Set the bottom thermostat to minimum.
Step 22
Set the top thermostat to maximum.
Step 23
The steps below assume that there is warm water in the tank. If the tank is cold or very hot, it may be difficult to get the expected changes when dialing in different temperatures on the thermostat.
Step 24
The rest of the steps will require power on for testing. Use extreme caution as the risk of shock injury is greatly increased if not fully paying attention. Ensure all wires are reconnected to respective terminals and there are no "accidental conductors" anywhere that could cause a short circuit or shock.
Step 25
Restore power to water heater.
Step 26
Remove red test lead from the "Ohms" or "Resistance" jack of the meter and insert into "Volt" jack.
Step 27
Set the range of the meter to the lowest Voltage value that is greater than 240 Volts "AC" or "VAC". As mentioned earlier, common voltages for residential (and mobile home / RV) type water heaters are: 120, 208 & 240, with the most common being the 240 volt variety. When steps below discuss measuring " line voltage ", substitute the voltage for your particular water heater instead.
Step 28

Check the top heating element's terminals for presence of line voltage by touching a probe tip to each terminal, as done in the resistance test earlier. Line voltage is likely 120, 208 or 240 in the U.S.
Step 29
If there is no power, attempt to reset the high temperature switch. It is a button either red or black, located directly above the thermostat. It most likely has "RESET" printed on it. With a screw driver or pencil, GENTLY but firmly press in. If it is tripped, a mechanical "click" should be felt or heard. A tripped high temp switch is indicative of a thermostat that will not open. More on this, later.
Step 30
After attempting reset, check the heating element for power again.
Step 31
If still no power present, test the top left and right terminals of the high temp switch for line voltage with the probe tips.
Step 32
If no power, trouble is an open circuit. Check the heater's "field wiring compartment" (usually located on the top of the heater), along the length of the cable that feeds the heater, and lastly inside the electrical panel. Remember, unless power is shut off at panel, this circuit is live at some point between the fuse or circuit breaker and the water heater. Tighten any and all wirenuts and connections in the wiring compartment all the way back to the terminals of the circuit breaker or fuses in the electrical panel. Replace open fuses or reset any tripped circuit breaker if off. Check for power at fuse or circuit breaker. A circuit breaker that immediately trips after resetting indicates a short circuit or less likely, defective circuit breaker.
Step 33
Once power is restored to top terminals of high temp switch, test for line voltage at heating element.
Step 34
If line voltage not found, replace top controls.
Step 35
Set top thermostat to minimum.
Step 36
Set lower thermostat to maximum.
Step 37
Check bottom heating element for presence of line voltage.
Step 38
If no power present, determine which wire is connects a heating element terminal screw to the bottom thermostat terminal screw. These will be the common screw terminals. The other screw on the thermostat and heating element will be the power screw terminals. Touch red probe to the power screw terminal of heating element and black probe to the power screw terminal of thermostat. Expect line voltage.
Step 39
If line voltage not found, replace upper controls.
Step 40
If line voltage found, check for line voltage at heating element terminal screws by touching each probe to the terminal screws.
Step 41
If line voltage not found, replace lower thermostat.
Step 42
If line voltage is found, wait for water to heat or perform the Ohms (or Resistance) checks on the elements once more with the power off. If line voltage is present on a heating element, it must heat the water unless the element has failed.
Step 43
Return all thermostats to an equal value of your choosing, but should not be set higher than 140 degrees.
Step 44
Replace insulation and access covers.